Metal Building Construction

Roof

The assembly used to test the thermal resistance of TempShield™ insulation as it would be installed in new metal building construction consisted of a corrugated metal exterior, 1/2" extruded polystyrene thermal breaks 5' on center, TempShield™ insulation, and 8" Z purlins commonly used in metal buildings.

Thermal Values Heat Flow
Up
Heat Flow
Down
U Value
Up
U Value
Down
K Value
Up
K Value
Down
TempShield™
w/Wafer Board
5.02 7.93 .199 .126 .199 .126
TempShield™
w/Metal Interior
4.29 7.29 .233 .137 .233 .137
TempShield™
Exposed to Interior
3.63* 7.26* .275* .138* .275* .138*

All Thermal Values are corrected for frame loss.
* Includes thermal resistance of 1.32 UP and 4.55 DOWN for interior air film.

Walls

Thermal assembly tested for thermal resistance of TempShield™ insulation in the walls of metal buildings consisted of corrugated metal exterior, 1/2" extruded polystyrene thermal breaks, TempShield™ insulation, 8" Z girts, and 1/2" wafer board to represent an interior finished wall.

Thermal Values Heat Flow Horz. U Value Horiz. K Value Horiz.
TempShield™ w/Wafer Board 5.45 .183 .183
TempShield™ w/Metal Interior 4.77 .210 .210
TempShield™ Exposed to Interior 4.50* .222* .222*

* Includes thermal resistance of 1.70 for interior air film.